The Velcon TP2 is recommended for installation on tap changers that:
- Perform a high number of operations
- Exhibit consistent sludging conditions
- Have a high tap to tap voltage difference
- Require frequent attention
Quality components and comprehensive design features have made the TP2 an industry standard for on-line filtration. All components are fully enclosed in a temperature controlled NEMA 4 cabinet. Operation of the unit is unattended and controlled by a user programmable timer. 3 gpm flow rate keeps turbulence in the reservoir to a minimum and allows for maximum filter life.
FEATURES
Self Draining – Reversible pump allows quick, no mess, filter changeout. No tools required.
Automatic Shut-off – Pressure switch turns the system off when filter is plugged. Relay can be wired to remote alarm or indicator light.
Oil Make-up – LTC reservoir can be topped off using 3- way valve oil make-up port.
Flexible Operation – Digital electronic timer can be programmed for multiple operating sequences. Internal battery keeps program in memory during power loss.
Hour Meter – Records run time of system to assure user of consistent operation.
Temperature Controlled – Cabinet heaters and fans keep extreme temperatures from affecting service and
prevent condensation build up.
SPECIFICATIONS
Mechanical
Flow Rate: 3 gallons per minute (USGPM).
Cabinet: NEMA 4 enclosure, galvanized steel, painted grey acrylic, easy-opening handle with lock and point latch, with louvers and filters, UL/CSA approved.
Pump: Heavy duty self-priming positive displacement pump with built in pressure relief valve.
Piping: Stainless steel tubing, JIC hydraulic fittings. External connections are 1/2” female npt.
Filter Vessel: Velcon Model VF-71E with manual vent and static pressure gauge is epoxy coated internally and externally. No tools required for filter changeout.
Filter: Velcon Model FO-718PL1/2 comes installed for removal of carbon contamination.
Sight Glass: 150 psi maximum working pressure for
oil flow indication.
Electrical
Motor: 1/2 hp, 120V, 1-phase, 1740 rpm, TEFC.
Control Box: NEMA 12 with high pressure switch, latching relay, forward/reverse switch, programmable timer, magnetic contactor, hour meter, and manual starter/disconnect with 10 amp heater overload.
Wiring: 16 ga., all terminal connections are XLA grade. Power Requirements: 120 vac, single-phase, 10 amps.
Heater and Fan: Adjustable setting, thermostaticallycontrolled.
ORDERING INFORMATION
Specify model number as shown below. Units are shipped with cartridge installed.
- System Part Number: TP2-1 120 v, 1 ph, 60 Hz
Also Available: 3 phase power, 50 Hz power (contact factory)
- Weight: 250 Ibs
- Shipping Weight: 325 Ibs
- Dimensions: Heigh: 43", Width: 30", Depth: 12"
- Crated Dimensions: Height: 47”, Width: 34”, Depth: 31”
OPTIONS & ACCESSORIES
| 643Y051 |
Door Mounted View Window |
| 241X051 |
3/4” JIC Port Connections (2 ea required) |
| 723Y005 |
No-Flow Shut-Off Switch |
| 552Y025 |
Stainless Steel Valve Upgrade |
| 605Y020 |
Timed Run Via Remote Start Signal From Tap Change |
| 031Y104 |
0.5 micron AC-7181/2 Cartridge for particle and free water removal |
| 031Y105 |
0.3 micron AC-718P3 Cartridge for particle and free water removal |
| 031Y106 |
0.3 micron FO-718PLP3 Cartridge for particle removal |
| 031Y102 |
0.3 micron SD-718P3 Superdri® Cartridge for particle and dissolved water removal |
RECOMMENDED SPARES
| FO-718PL1/2 |
Filter Cartridge, box of 6 ea (or:) |
| FO-718PLP3 |
Filter Cartridge, box of 6 ea (or:) |
| AC-7181/2 |
Aquacon® Cartridge, box of 6 ea (or:) |
| AC-718P3 |
Aquacon®Cartridge, box of 6 ea (or:) |
| SD-718P3 |
Superdri® Cartridge, box of 6 ea |
| G-1016 |
Filter Housing Lid Gasket, 1 ea |
|